48-7009-E 5-33
Where contact outputs are desired to be provided when a measurement value comes to a target value
(SV start)
Setting example for output 1 to be provided for 1 minute after 180 °C is reached
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
180C
180
SEt5
oUt1
Name
Setting content
Setting value
o1F
Target connection setting
Timer 1 output
5
SEt04
tIME1
Name
Setting content
Setting value
tMF1
Function setting
SV start
3
tSV1
Start SV permissible range setting
Give range of 2 °C
2
oFt1
Off delay timer
1 minute
00:01
Temperature
180℃
Normal
temperature
Output 1
ON
OFF
Contact output is provided for 1 minute
Setting the start SV permissible range
setting to 2 °C results in timer
operation when the value falls in the
range of SV ± 1 .