Toho-electronics TTM200 Uživatelský manuál Strana 201

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 264
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 200
48-7009-E 6-53
Event function 3 setting (CT abnormality)
SEt05
oUt1
to
SEt11
oUt7
Setting content
Initial value
8
E1F3
to
E7F3
Function
000
**0
None
**1
CT 1 abnormality
**2
CT 2 abnormality
**3
CT 1 abnormality + CT 2 abnormality
Add-on function
*0*
None
*1*
Hold
*2*
Delay
*3*
Hold + delay
Control mode interlocking function
0**
All modes
1**
RUN/MAN mode only
2**
RUN mode only
Set the event function 3 (CT abnormality).
Event function 3 is a function to detect the current flowing in the heater that is assigned in the outputs 1 to 7 as target
connections, using the current transformer (CT) that is supplied as an accessory, and to compare the detected current to the CT
abnormality current.
This function is useful for detecting disconnected wiring to the heater or adhesion of a relay contact that turns on and off the
electricity to the heater.
For the details regarding the connection and setting of CT (current transformer), please refer
to Operation Manual CT (P5-40 to 44).
Zobrazit stránku 200
1 2 ... 196 197 198 199 200 201 202 203 204 205 206 ... 263 264

Komentáře k této Příručce

Žádné komentáře