  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 177
48-7009-E 6-30
Primary control off-point position selection setting
SEt04
CNt
Setting content
Initial value
32
CMod
0
SV unit setting
0
1
Upper
2
Middle
3
Lower
Set the primary control off-point position selection.
Set the selection setting to 0 for allowing to set the off-point position of sensitivity in the SV setting unit of °C and such.
Set the selection setting to 1 to 3 for automatically setting the off-point position of the primary control to upper, middle or
lower position with respect to SV.
<Reverse operation>
Cmod = 0 (SV)
C1
CP1
CP2
C2
+db
ON
OFF
PV
Low
SV
High
Cmod = 1 (upper)
C1
db
C2
ON
OFF
PV
Low
SV
High
Cmod = 2 (middle)
C1
db
C2
ON
OFF
PV
Low
SV
High
Cmod = 3 (lower)
C1
db
C2
ON
OFF
PV
Low
SV
High
C1: Sensitivity setting 1
C2: Sensitivity setting 2
CP1: Off-point setting 1 = negative value
CP2: Off-point setting 2 = positive value
db: Dead band = positive value
C1: Sensitivity setting 1
C2: Sensitivity setting 2
db: Dead band = positive value
C1: Sensitivity setting 1
C2: Sensitivity setting 2
db: Dead band = positive value
C1: Sensitivity setting 1
C2: Sensitivity setting 2
db: Dead band = positive value